- Application
- Firecel SR 114H is primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance is required.
- Standards
-
BS 5839-1:2002
Code of practice for fire system design, installation, commissioning and maintenance. -
BS 7629-1:2008
Low emission of smoke and corrosive gases -
BS EN 50200 PH30 (all sizes)
Temperature: 830°C
Flame and shock for 30 minutes. -
BS EN 50200 PH60 (1.5mm² and above)
Temperature: 830°C
Flame and shock for 60 minutes. -
BS 6387
Category C-W-Z
C - Resistance to fire at 950ºC for 3 hours
W - Resistance to fire with water at 950ºC for 3 hours
Z - Resistance to fire with mechanical shock at 950ºC for 3 hours -
EN 50200 Annex E (previously BS 8434-1: 2003)
Temperature: 830°C
Flame and shock for 15 minutes.
+ flame, shock and water for 15 minutes.
LPCB Approved - Conductor
-
Plain annealed copper to BS EN 60228:2005 (previously BS6360). Solid (Class 1) for 1 - 1.5 - 2.5mm2*. Stranded (Class 2) for 4mm2.
*1.5 - 2.5mm2 are available with stranded conductors (Class 2) (SR 114H-R) - Insulation
- High performance silicone rubber El2 to BS EN 50363-1
- Electrostatic Screen
- Aluminium/polyester tape. 125% coverage.
- Earth Conductor
- Tinned annealed copper to BS EN 60228:2005 (previously BS6360) (drain wire for multicore cables.)
- Sheath
- LSZH thermoplastic material Type LTS3 to BS 7655-6.1.
- Sheath Colour
- White or Red
- Voltage Rating
- 300/500V
- Operating Temperature
- -40°C to +90°C
- Minimum Bending Radius
- 6 × Overall Diameter
- Core Identification
-
2 Cores + E: Blue, Brown
3 Cores + E: Brown, Black, Grey
4 Cores + E: Blue, Brown, Black, Grey
7 Cores*: Centre: Brown
1st Layer: Brown, Black, 4 × White
12 cores*: Centre: Brown, Black, White
1st Layer: Brown, Black, 7 × White
19 cores*: Centre: Brown
1st Layer: Brown, Black, 4 × White
2nd Layer: Brown, Black, 10 × White
- Note*:
- Numbered Cores available on request.
- Installation
- Firecel Cable is easy to handle and install without the need for specialist equipment. The cable can be attached directly to a surface using LSZH coated copper P clips, available with the cables. Plastic clips can not be used. Firecel Cable can also be installed directly into trays or conduit, or buried in plaster. Firecel Cable is suitable for use in protected outdoor environments.
|
No. of Cores × Cross Sectional Area # mm² |
Conductor Size #/mm |
Nominal Overall Diameter mm |
Net Weight (kg/km) |
|---|---|---|---|
| 2 × 1.0 | 1/1.13 | 7.1 | 70 |
| 3 × 1.0 | 1/1.13 | 8.0 | 85 |
| 4 × 1.0 | 1/1.13 | 8.3 | 110 |
| 2 × 1.5 | 1/1.38 | 8.0 | 95 |
| 3 × 1.5 | 1/1.38 | 8.5 | 115 |
| 4 × 1.5 | 1/1.38 | 9.4 | 150 |
| 2 × 2.5 | 1/1.75 | 9.4 | 135 |
| 3 × 2.5 | 1/1.75 | 10.0 | 170 |
| 4 × 2.5 | 1/1.75 | 11.0 | 210 |
| 2 × 1.5 | 7/0.53 | 8.4 | 106 |
| 3 × 1.5 | 7/0.53 | 8.9 | 134 |
| 4 × 1.5 | 7/0.53 | 9.8 | 166 |
| 2 × 2.5 | 7/0.67 | 9.9 | 145 |
| 3 × 2.5 | 7/0.67 | 10.3 | 180 |
| 4 × 2.5 | 7/0.67 | 11.8 | 250 |
| 2 × 4.0 | 7/0.85 | 11.5 | 210 |
| 3 × 4.0 | 7/0.85 | 12.2 | 260 |
| 4 × 4.0 | 7/0.85 | 13.5 | 330 |
| 7 × 1.0 | 1/1.13 | 10.0 | 165 |
| 7 × 1.5 | 1/1.38 | 11.3 | 225 |
| 12 × 1.0 | 1/1.13 | 12.5 | 255 |
| 12 × 1.5 | 1/1.38 | 14.5 | 350 |
| 19 × 1.0 | 1/1.13 | 15.0 | 380 |
| 19 × 1.5 | 1/1.38 | 17.0 | 520 |